| Input Voltage |
90 ~ 264VAC 127 ~ 370VDC |
| Input Frequency |
47 ~ 63Hz |
| Input Current |
2A/115VAC 1.2A/230VAC |
| Inrush Current |
35A/115VAC 70A/230VAC cold start |
| Leakage Current |
<1mA/ 240VAC |
| Set Up, Rise Time |
2400ms, 20ms/230VAC 2400ms, 20ms/115VAC at full load |
| Hold Up Time |
40ms/230VAC 15ms/115VAC at full load |
| Over Load Protection |
105 ~ 150% rated output power |
|
Hiccup mode, recovers automatically after fault condition is removed |
| Over Voltage Protection |
Shut down o/p voltage, re-power on to recover |
| AC OK Alarm |
Relay contact output, ON : AC OK ; OFF : AC Fail ; Max. Rating : 30V / 1A |
| Battery Low Alarm |
Relay contact output, ON : Battery OK ; OFF : Battery Low ; Max. Rating : 30V / 1A |
| Working Temperature |
-20°C ~ +70°C (Refer to output load derating curve) |
| Working Humidity |
20 ~ 90% RH non-condensing |
| Storage Temperature, Humidity |
-20°C ~ +85°C, 10 ~ 95% RH |
| Temperature Coefficient |
±0.03%/°C (0~50°C) on CH1 output |
| Vibration |
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes |
| Withstand Voltage |
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC |
| Isolation Resistance |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC/ 25/°C 70% RH |
| Safety Standards |
UL60950-1, TUV EN60950-1 approved |
| EMC |
Compliance to EN55022 (CISPR22) Class B; EN61000-3-2,-3; ENV50204; |
|
EN61000-4-2,3,4,5,6,8,11; EN55024, light industry level, criteria A |
| MTBF |
417.6K hrs min. MIL-HDBK-217F (25°) |
| Dimensions |
127 x 76.2 x 31mm |