| Voltage Range |
90~264Vac 135~370Vdc |
| Input Frequency |
47~63Hz |
| Input Current |
1.5A/100Vac |
| Inrush Current |
90A/230Vac |
| Leakage Current |
0.5mA/240Vac |
| Votage Adj. Range |
Fixed |
| Line Regulation |
±1.0% |
| Setup, Rise, Hold Up Time |
300mS, 50mS, 16mS at full load |
| Over Load Protection |
R1B~2P1J : 112 ~ 250% rated output power ; 3P1J~8P1J: 150~350% rated output power. |
|
Hiccup mode, recovers automatically after fault condition is removed |
| Over Voltage Protection |
110~150% rated output voltage |
|
Hiccup mode, recovers automatically after fault condition is removed |
| Over Temperature Protection |
Tj 135°C typically (IC1) detect on main control IC |
|
Will shut down o/p voltage, recovers automatically after temperature goes down |
| Working Temperature |
0°C to +65°C (refer to derating curve) |
| Working Humidity |
20% to 90% RH, non-condensing |
| Storage Temp., humidity |
-20°C to +85°C, 10% to 95% RH |
| Temp. Coefficient |
±0.03%/°C (0°C to 50°C) |
| Vibration |
10 to 500Hz, 2G 10min./1 cycle, period for 60min. each along X, Y, Z axes |
| Withstand Voltage |
I/P-O/P: 5656VDC, I/P-FG: 2828VDC |
| Isolation Resistance |
I/P-O/P, I/P-FG: 100MOhms/ 500VDC |
| Safety Standards |
UL2601-1, IEC60601-1, EN60601-1 Approved |
| EMC |
Compliance to EN55011 (CISPR11) Class B; EN61000-3-2,3; |
|
EN60601-1-2 (EN61000-4-2,3,4,5,6,8,11) Light industry level, criteria A |
| DC Plug |
3.3~7.5V 5 Pin Din Connector |
|
Others 2.1 x 5.5 x 11mm, center positive, hollow plug |