SCN-1K5-12 - SCN-1K5-12
Home > Products > SCN-1K5 Series 1500W Single Output AC-DC Parallel Function Enclos > SCN-1K5-12
|
Standards
|
General Specifications
| VOLTAGE ADJ. RANGE |
?5.0% typical adjustment by potentiometer 20~100% adjustment by 1~5VDC external control |
| SETUP, RISE, HOLD TIME |
800ms, 50ms, 16ms at full load |
| VOLTAGE RANGE |
200 ~ 260VAC 290~370VDC |
| FREQUENCY RANGE |
47~63Hz |
| AC CURRENT |
12A / 230VAC |
| INRUSH CURRENT (max.) |
120A / 230VAC |
| LEAKAGE CURRENT(max.) |
3.5mA / 240VAC |
| OVER LOAD |
110~135% rated output power Protection type : Current limiting, delay shut down o/p voltage, re-powe |
| OVER VOLTAGE |
110~135% follow to output set up point Protection type : Shut down o/p voltage, re-power on to recov |
| OVER TEMPERATURE |
>100?C / measure by heat sink, near transformer Protection type : Shut down o/p voltage, re-power on |
| WORKING TEMP. |
-10~+65?C (Refer to output load derating curve) |
| WORKING HUMIDITY |
20%~90% RH non-condensing |
| STORAGE TEMP., HUMIDITY |
-20~+85?C 10~95% RH |
| TEMP. COEFFICIENT |
?0.04% /?C (0~50?C) |
| VIBRATION |
10~200Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes |
| SAFETY STANDARDS |
Design refer to UL1950, CSA22.2, IEC60950 |
| WITHSTAND VOLTAGE |
I/P-O/P, :1500VAC I/P-F |
| ISOLATION RESISTANCE |
I/P-O/P, I/P-FG, >100M Ohms / 500VDC |
| EMI CONDUCTION & RADIATION |
Design refer to FCC part 15 class A |
| MTBF |
60khrs min. MIL-HDBK-217F (25?C) |
| SPECIAL FUNCTION |
DC voltage adj., Remote sensing, remote control, parallel operation (refer to terminal instruction m |
|
SCN-1K5-12
|
Safety Model No
|
DC Voltage
|
Rated Current
|
Current Range
|
Rated Power
|
Ripple & Noise
|
Voltage Tolerance
|
Line Regulation
|
Load Regulation
|
Efficiency
|
|
1K5S-N012
|
12V
|
125A
|
0-125A
|
1500W
|
120mVp-p
|
±1.0%
|
±0.5%
|
±0.5%
|
83%
|
|
 |