SCN-600-48 - SCN-600-48
Home > Products > SCN-600 Series 600W Single Output AC-DC Parallel Enclosed Power S > SCN-600-48
|
Standards
|
General Specifications
| VOLTAGE ADJ. RANGE |
?5.0% typical adjustment by potentiometer 20~100% adjustment by 1~5VDC external control |
| SETUP, RISE, HOLD TIME |
800ms, 50ms, 16ms at full load |
| VOLTAGE RANGE |
90 ~ 130VAC / 180~260VAC selected by switch,260~370VDC |
| FREQUENCY RANGE |
47~63Hz |
| AC CURRENT |
11A / 115VAC 7.0A / 230VAC |
| INRUSH CURRENT (max.) |
60A / 230VAC |
| LEAKAGE CURRENT |
3.5mA / 240VAC |
| OVER LOAD |
101~115%/110~135% rated output power Protection type : Current limiting, delay shut down o/p voltage |
| OVER VOLTAGE |
110~135% follow to output set up point Protection type : Shut down o/p voltage, re-power on to recov |
| OVER TEMPERATURE |
>100?C / measure by heat sink, near transformer Protection type : Shut down o/p voltage, re-power on |
| WORKING TEMP. |
-10~+65?C (Refer to output load derating curve) |
| WORKING HUMIDITY |
20%~90% RH non-condensing |
| STORAGE TEMP., HUMIDITY |
-20~+85?C , 10~95% RH |
| TEMP. COEFFICIENT |
?0.04%/?C (0~50?C) |
| VIBRATION |
10~200Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes |
| SAFETY STANDARDS |
UL1950, CSA22.2, IEC60950 Approved |
| WITHSTAND VOLTAGE |
I/P-O/P, I/P-FG:1500VAC |
| ISOLATION RESISTANCE |
I/P-O/P, I/P-FG, 100M Ohms / 500VDC |
| EMI CONDUCTION & RADIATION |
Compliance to FCC part 15 class A |
| MTBF |
120khrs min. MIL-HDBK-217F (25?C) |
| SPECIAL FUNCTION |
DC voltage adj., Remote sensing, remote control, parallel operation (refer to terminal instruction m |
|
SCN-600-48
|
Safety Model No
|
DC Voltage
|
Rated Current
|
Current Range
|
Rated Power
|
Ripple & Noise
|
Voltage Tolerance
|
Line Regulation
|
Load Regulation
|
Efficiency
|
|
600S-N048
|
48V
|
12A
|
0-12A
|
600W
|
480mVp-p
|
±1.0%
|
±0.5%
|
±0.5%
|
87%
|
|
 |
| Add this product to your ClipBook |