| Input Voltage |
85 ~ 264Vac 120 ~ 370Vdc |
| Input Frequency |
47 ~ 63Hz |
| Power Factor |
PF>0.93/230Vac PF>0.98/115Vac at full load |
| Input Current |
2.5A/115Vac 1.2A/230Vac |
| Inrush Current |
40A/230Vac, cold start |
| Leakage Current |
<2mA/ 240Vac |
| Setup, Rise Time |
600ms, 30ms at full load |
| Hold Time |
20ms at full load |
| Over Load Protection |
105 ~ 150%rated output power |
|
Constant current limiting, recovers automatically after fault condition is removed |
| Over Voltage Protection |
Shut down o/p voltage, re-power on to recover |
| Over Temperature Protection |
95°C ±5°C (TSW1 : Detect on heatsink of power transistor) |
|
Shut down o/p voltage, recovers automatically after temperature goes down |
| Remote Control |
CN1:4 ~ 10Vdc Power On, <0 ~ 0.8Vdc Power Off |
| Working Temperature |
-10°C ~ +60°C (Refer to output load derating curve) |
| Working Humidity |
20 ~ 90% RH non-condensing |
| Storage Temperature, Humidity |
-20°C ~ +85°C, 10 ~ 95% RH |
| Temperature Coefficient |
±0.05%/°C (0 ~ 50°C) |
| Vibration |
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X,Y, Z axes |
| Withstand Voltage |
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC |
| Isolation Resistance |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC |
| Safety |
UL60950-1,TUV EN60950-1 and S-MARK J60950 Approved |
| EMC |
Compliance to EN55022 (CISPR22) Class B; EN61000-3-2,-3; |
|
EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, Light industry level, criteria A |
| MTBF |
191.2K hrs min. MIL-HDBK-217F (25°C) |