MDR-60 Series is a slim line DIN rail Class I switching power supply. Designed with a fully isolated plastic case to prevent user contact and the risk of shock. Featuring up to 85% efficiency this series can be cooled using only free air convection up to 70°C which significantly increases the reliability and lifetime of the power supply. Other standard features include its low no load power consumption, to save energy, short circuit, over load and over voltage protections and the DC OK relay contact for monitoring the status of the PSU.
| Input Voltage | 85 ~ 264Vac 20 ~ 370Vdc |
|---|---|
| Input Frequency | 47 ~ 63Hz |
| Input Current | 1.8A/115Vac 1A/230Vac |
| Inrush Current | 30A/115Vac 60A/230Vac, cold start |
| Leakage Current | <1mA at 240Vac |
| Set Up, Rise Time | 500ms, 30ms/230Vac 500ms, 30ms/115Vac at full load |
| Hold Time | Typically 50ms/230Vac 20ms/115Vac at full load |
| Over Load Protection | 105 ~ 150% rated output power |
| Constant current limiting, recovers automatically after fault condition is removed | |
| Over Voltage Protection | Shut down output voltage, re-power on to recover |
| Working Temperature | -20°C to +70°C (Refer to output load derating curve) |
| Working Humidity | 20 ~ 90% RH non-condensing |
| Storage Temperature, Humidity | -40°C to +85°C, 10 ~ 95% RH |
| Temperature Coefficient | ±0.03%/°C (0 ~ 50°C) |
| Vibration | Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes |
| Mounting: Compliance to IEC60068-2-6 | |
| Withstand Voltage | I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC |
| Isolation Resistance | I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC |
| Safety Standards | UL508, TUV EN60950-1 Approved |
| EMC | Compliance to EN55011; EN55022 (CISPR22) Class B; EN61000-3-2,-3; ENV50204; |
| EN61000-4-2,3,4,5,6,8,11; EN55024; EN61000-6-1; EN61204-3 Light industry level, criteria A | |
| MTBF | 299.2K hrs min. MIL-HDBK-217F (25°C) |