| Input Voltage |
90 ~ 264Vac 127 ~ 370Vdc |
| Input Frequency |
47 ~ 63Hz |
| Power Factor |
0.95/230Vac 0.98/115Vac at full load |
| Input Current |
12A/115Vac 5.2A/230Vac |
| Inrush Current |
25A/115Vac 50A/230Vac |
| Leakage Current |
<3.5mA/ 240Vac |
| Battery Type |
Open & Sealed Lead Acid |
| Reverse Current |
<1mA |
| Over Voltage Protection |
Shut down o/p voltage, re-power on to recover |
| Over Temperature Protection |
Shut down o/p voltage, recovers automatically after temperature goes down |
| Short Circuit Protection |
Protected by internal circuit |
| Reverse Polarity |
Protected by internal circuit |
| Remote Control |
Open: Normal work Short: Stop Charging |
| Battery Banks |
2 banks (A & B) |
| Fast Charge |
2 / 8 stage select |
| Charging OK |
Relay contact rating (max.): 30V/1 Aresistive; |
|
Short: when the unit is working properly, Open: when the unit stop charging |
| Output OK |
Relay contact rating (max.): 30V/1Aresistive; |
|
Short: when the battery is full, Open: when the battery is still charging |
| Temperature Compensation |
By NTC, compensate both banks at the same time |
| Working Temperature |
-20°C ~ +60°C (Refer to output load derating curve) |
| Working Humidity |
20 ~ 90% RH non-condensing |
| Storage Temperature, Humidity |
-40°C ~ +85°C, 10 ~ 95% RH |
| Temperature Coefficient |
±0.05%/°C (0 ~ 50°C) |
| Vibration |
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes |
| Withstand Voltage |
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC |
| Isolation Resistance |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC 25°C 70%RH |
| Safety Standards |
UL60950-1, TUV EN60950-1 approved |
| EMC |
Compliance to EN55022 (CISPR22); EN61000-3-2,-3; ENV50204; |
|
EN61000-4-2,3,4,5,6,8,11; EN55024, light industry level, criteria A |
| MTBF |
127.4Khrs min. MIL-HDBK-217F (25°C) |