AD-55 Series is a 55W single output AC/DC power supply with battery charger (UPS) Function that meets UL, TUV, CB & CE requirements. AD-55 Series also has standard features such as short circuit, over load and over load protections as well as optional battery low protections and alarm signals. Suitable applications include control panels, back-up systems.
| Input Voltage | 88 ~ 264Vac 120 ~ 370Vdc |
|---|---|
| Input Frequency | 47 ~ 63Hz |
| Input Current | 1.6A/115V, 1.0A/230V |
| Inrush Current | 20A/15V, 40A/230V cold start |
| Leakage Current | <1mA/240Vac |
| Setup, Rise Time | 800ms, 50ms/230Vac 1600ms, 50ms/115Vac at full load |
| Hold Up Time | 80ms/230Vac 16ms/115Vac at full load |
| Over Load Protection | 105%~150% rated output power |
| Hiccup mode, recovers automatically after fault condition is removed | |
| Over Voltage Protection | Hiccup mode, recovers automatically after fault condition is removed |
| DC Alarm Signal (Optional) | AC fail CN1 PIN2 |
| Battery low under charge voltage 82.5% ±2% CN1 PIN1 | |
| Normal 0.8V max.Abnormal 5V ±0.5V | |
| Working Temperature | -10°C ~ +60°C (Refer to output load derating curve) |
| Worhing Humidity | 20 ~ 90% RH non-condensing |
| Storage Temperature, Humidity | -20°C ~ +85°C, 10% ~ 95% RH |
| Temperature Coefficient | ±0.03% /°C (0~50°C) on 1st output |
| Vibration | 10 ~ 500Hz, 2G 10min./1 cycle, 60min. each along X, Y, Z axes |
| Withstand Voltage | I/P-O/P:3KVAC, I/P-FG:1.5KVAC, O/P-FG:0.5KVAC |
| Isolation Resistance | I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC |
| Safety Standards | UL60950-1, TUV EN60950-1 Approved |
| EMC | Compliance to EN55022 (CISPR22) Class B; EN61000-3-2,-3; ENV50204; |
| EN61000-4-2,3,4,5,6,8,11; EN55024, Light industry level, criteria A | |
| MTBF | 304.3K hrs min. MIL-HDBK-217F (25°C) |